Karakteristik saklar pemutus beban Gas 15KV SF6

  • 15KVSakelar pemutus dipasang di tiangTerbuat dari bahan yang terbukti tahan lama, tahan korosi. (Pelat baja tahan karat 304L untuk kapal perang), memastikan masa pakai yang panjang (30 tahun), sakelar pemutus beban 15KV Kami dapat menjalankan serangkaian operasi, dengan karakteristik ideal peralatan atas tiang.

  • Masing-masingGoower15kv load break switch telah diisi dengan gas sf6 sebelum meninggalkan pabrik, perawatan disegel. Tes sakelar pemutus pemasangan tiang 15 kv dilakukan sesuai dengan IEC60265-1 (1988) GB 3804-1990 standar.


SF6 Gas 15KV Load Break Switch In Pole Mounted Switch Solution

15kv load break switch has a certain interrupting capacity because of the interrupting device, but 15 kv pole mounted disconnect switch is not as strong as the interrupting capacity of the circuit breaker, which can split the normal working current, and in the case of short circuit, he can only silently withstand the short circuit current, and if this time the manual or electric breaking may explode, so the load switch is generally used together with the current limiting fuse (load switch + fuse is not the standard configuration, and can also be used without fuse) In the event of an overload or short circuit, the circuit is broken by a fuse. In order to save costs, the load switch + fuse can replace the circuit breaker. Inquiry more pole top switches


Specification of 15 KV Pole Mounted Disconnect Switch

Products Type
FWX-15
Basic Ratings
Maximum System Voltage15KV
Rated Continuous Current630A
Rated Frequency50/60Hz
Short Time Withstand CurrentIKA/sec
Making and Breaking Capacity
Mainly Active LoadCurrent630A
Number of Load-break Operations400times
Short-circuit Making Current(peak)50KA


Number of Making Operations on 15 KV Pole Mounted Disconnect Switch

Number of Making Operations

5 times

Cable Charging Current

lOA

Line Charging Current

lOA

Closed Loop Circuit Current

630A

Transformer Magnetizing Current

22A

Power Frequency Withstand Current Test

Wet Condition- 10 sec (Ph- Ph-Eth, Across Interrupters)

50KV

DryCondition- I min ( Phase to Phase, Phase to Earth)

50KV

Dry Condition - 1 min (Across Interrupter )

60KV

Impulse Withstand Current Test(1.2 x 50 µs)


Internal Arc Test of 15 KV Pole Mounted Disconnect Switch

Internal Arc Test

20kA /0.1 sec

Arc Extinction Medium

SF6 Gas

Insulation Medium

SF6 Gas

Creepage Distance (Porcelain)

560mm

IP Level

54

Operation Performance

Closing/Opening Tin

< O. l sec

Mechanica l Operations (Guaranteed)

l OOOO times

Operating Temperature.1re(*Manual Type)

-25~+70℃

Gas Pressure

Nominal Pressure (kg/cm2 G, at 20°C)

0.07

Bursting Pressure (kg/cm2 G)

4 ~  6

Minimum Gas Pressure (kg/cm2 G)

0.0

Leakage  Rate (cc/ sec)

1%


Other Ratings & Specifications of 15 KV Pole Mounted Disconnect Switch

Other Ratings & Specifications

Internal Arc Test

20kA /0.1 sec

20kA /0.1 sec

20kA /0.1 sec

Arc Extinction Medium

SF6 Gas

SF6 Gas

SF6 Gas

Insulation Medium

SF6 Gas

SF6 Gas

SF6 Gas

Creepage Distance (Porcelain)

380mm

700mm

1055mm

Creepage Distance (Silicon)

780mm

1200mm

1550mm

Dry arcing distance

≥200mm

IP Level

65

65

65

Operation Performance

Closing/Opening Time

<1sec

<1sec

<1sec

Mechanical Operations (Guaranteed)

10000times

10000times

10000times

Operating Temperature (*Manual Type)

-25~+70℃

-25~+70℃

-25~+70℃

Gas Pressure

Nominal Pressure (MPa, at 20°C)

0.07

0.07

0.07

Bursting Pressure (MPa)

0.4~0.6

0.4~0.6

0.4~0.6

Minimum Gas Pressure (MPa)

0.05

0.05

0.05

Leakage Rate (cc/ sec)

≤0.5%

≤0.5%

≤0.5%

Voltage sensors

CT ABC   10P10   5VA

400:5

400:5

400:5

Incoming side and outgoing side of the voltage sensor

6 Voltage sensor(built-in)                    Phase voltage:(24(36)kV/√3)/(3.25V/√3)


Special attention should be paid to the voltage sensor, which must be directly fed by the 15kv load break pole mounted disconnect switch. No additional adjustment circuit can be added to the controller. The voltage signal of the switch into the test line needs to be tested separately.